PGS Series Outdoor High Voltage SF6 Load Break Switch

PGS Series Outdoor High Voltage SF6 Load Break Switch

Application

PGS-630A pole mounted load break switch is used for breaking rated voltage 12/24/40.5kV, rated current 630A, 50/60Hz power distribution system, closing load current and over load current of power system, it could separate automatically track sections of power distribution which faults occur. The switch is matched with electronic controller which is with the latest technology. The switch has manual, motor, remote operation modes. The electronic controller would be installed inside the stainless steel box, so it could be used in various climate conditions. Besides that, the wire/wireless modem installed inside control box could achieve remote monitoring and controlling. It’s easy and convenient for installation the switch on pole, and that could reduce the execution cost.

Specifications

Environmental Conditions

Air temperature: -40℃~+50℃;

Relative humidity: 110%

Altitude ≤3000m.

Wind pressure ≤700pa (equivalent to wind speed 34m/s).

Seismic intensity: 8 degree.

Installation site: No fire disaster, explosion danger, chemical corrosion and frequent strenuous vibration places).

Pollution grade: Ⅲ class, Ⅳclass.

 

Type descriptions

Parameter

Technical Parameter

Products TypePGS-12PGS-24PGS-40.5
Basic Ratings
Maximum system voltage15KV25.8KV40.5KV
Rated continuous current630A630A630A
Rated frequency50/60Hz50/60Hz50/60Hz
Short time withstand current20KA/4s25KA/1s20KA/1s
Making and Breaking Capacity
Mainly active load current630A630A630A
Number of load-break operations400times400times400times
Short-circuit making current (peak)50KA50KA50KA
Number of making operations5 times5 times5 times
Cable charging current25A25A25A
Line charging current1.5A1.5A2A

Closed loop circuit current630A630A630A
Rated no-load transformer breaking current22A22A22A
Power Frequency Withstand Current Test
10s(wet test),phase- phase-earth, across open contacts45KV50KV70KV
1min(dry test), earth, phase to earth50KV60KV95KV
1min(dry test), across open contacts50KV60KV110KV
Impulse Withstand Current Test( 1.2 x 50 µs )
Phase-to-phase, phase-to-earth85KV150KV195KV
Across open contacts95KV150KV215KV
Other Ratings & Specifications
Internal arc test20kA /0.1 s20kA /0.1 s20kA /0.1 s
Arc extinction mediumSF 6 GasSF 6 GasSF 6 Gas
Insulation mediumSF 6 GasSF 6 GasSF 6 Gas
Creepage distance (porcelain)550mm840mm1055mm
Creepage distance (silicon)610mm900mm1250mm
IP level545454
Operation Performance
Closing/opening time<1sec<1sec<1sec
Mechanical operations (guaranteed)10000times10000times10000times
Operating temperature (*manual type)-25(-40)~70℃-25(-40)~70℃-25(-40)~70℃
Gas Pressure
Rated working pressure (kg/cm2 G, at 20°C)0.71.01.0
Explosion-protection equipment action pressure (kg/cm2 G)4~64~64~6
Minimum working pressure (kg/cm2 G)0.050.00.0
Gas leakage rate (cc/ s)≤1%≤1%≤1%

Overall Dimensions

Dimension(mm)InstallationDimension(mm)Packing size(mm)Creep distance ofbushing(mm)
ABCLength × WidthLength×Width×high
10KV225435500500×3901100×900×700556
24KV300435500500×3901300×1100×700840
40.5KV350435500700×3901400×1200×7001250

PDF Download

PDF Download