FZN25-12 Series Indoor High Voltage Vacuum Load Break Switch

FZN25-12 Series Indoor High Voltage Vacuum Load Break Switch

Application

FZN25-12 indoor HV vacuum load break switch a 3-phase AC 50Hz 12kV indoor switch equipment.

♦ Operating mechanism: spring operating mechanism, manual type and electrical type available;

♦ Operation type: right operati on an d left operation;

♦ Operation direction: left operation, right operation;

♦ Application: indoor 12kv switchgear.

Specifications

Environmental Conditions

Ambient temperature: -25°C 〜+40°C;

Altitude: <1000m (above sea level);

Relative humidity: daily average <95%, monthly average <90%;

Earthquake intensity: <8 level;

Pollution grade: II;

Installation place without fire, explosion, chemical corrosion and serious vibration.

 

Parameter

Main technical parameters

NOItemUnitFZN25-12LT

630-20

FZRN25-12D/T

200-31.5

1Rated voltagekV1212
2Rated frequencyHz5050
3Rated currentA630200
41min power frequency withstand voltage (Phase to earth,Phase-to-earth, phase-to-phasekV4242
 between poles, open contacts)Isolating fracture 4848
5Rated lightning impulse withstand voltage (Phase toPhase-to-earth, phase-to-phasekV7575
earth, between poles, open contacts)Isolating fracture8585
6Rated short time withstand current (thermal stability current)Load break switchkA20 
7Rated short circuit duration

( thermal stability time)

Load break switchs4 
8Rated short circuit making current (peak)kA50 
9Rated active load breaking currentA630 
10Rated loop breaking current630 
11Rated cable charging current 10 
12Rated no-load transformer capacitykVA16001600
13Rated short circuit breaking current (limit current fuse)kA 31.5
14Rated breaking transfer currentA 2000
15Fuse model  SDLAJ-12

SFLZJ-12

16Striker output energyJ 2-5

NOItemUnitFZN25-12D/T

630-20

FZRN25-12D/T

200-31.5

17Auxiliary circuit rated voltageV^110 ^220^110 ^220
18Earth switch rated short time withstand currentkA2020
19Earth switch rated peak short circuit durationS22
20Earth switch rated peak withstand currentkA5050
21Rated short making currentkA5080(prospective peak value)
22Mechanical lifetimes1000010000

Mechanical property

NOItemUnitValue
FZN25-12

D/ T630 20

FZRN25-12

D/T200-31.5

1Air clearance between charged parts and to earthmm>125
2Conducting tube insert into fixed contact holder depthmm>18
3Vacuum interrupter open distancemm600+1
4Vacuum interrupter contact spring compression lengthmm20+1
5Vacuum interrupter average closing speedm/s0.6±0.2
6Vacuum interrupter average opening speedm/s1.0±0.2
7Closing bouncing timems<2
8Three phase closing and opening synchronismms<3
9Main circuit resistancerQ<150<300
10Manual opera+’on maximum torquen.m<160
11Fuse trigger opening timems30-40
12Release trigger opening timems40-45

Energy storage motor parameters

ModelRated voltage VRated current ARated power WNormal working voltage range
LLZY-CJ01B8AC/DC2200.77085%-110% rated
66ZY-CJ028AC/DC1101.5voltage

General Structure Drawing and Installation Size (unit: mm)

1. Cabinet bracket 2. Disconnector 3. Fuse 4. Insulated tension pole5. Upper bracket 6. Vacum interrupter 7. Static contact 8. Insulator9. Grounding knife 10. Grounding knife spring 11.Opening spring12. The tripping driving device 13. Insulated tension pole 14. Main axle15.Layshaft 16. Adjusting yoke 17. Spring operating mechanism 